SELF-DIAGNOSIS state

SELF-DIAGNOSIS

During the startup, after scanning the system led's, the controller performs a series of self-diagnostic operations. When any faults are detected or the operator has to be informed of any given situation, the self-doagnosis procedure is temporarily interrupted, signalling the event.
The fault signal is made by led's L1, L2 and a message is given on display (if present).

System Messages
n.Led ONSystem Message (if display present)DescriptionType
1led_on.jpg L1System Data WRITE ERRORIndicates that a write error has occurred during the configuration data saving. B
2led_on.jpg L2System Data IS RESTORED FROM DEFAULTIndicates that the configuration data has been restores to the default settings. C
3led_on.jpg L1
led_on.jpg L2
System Data is updated
Please verify new data
Indicates that the configuration data has been converted into a new format. Check that the previous settings have been maintained. C
4led_on.jpg L3Firmware is updated
old: 1K31F10 1.001
new: 1K31F10 1.002
Indicates that a firmware update has been made. C

When the condition detected allows to continue to the start stage (type C) and waits for the FUNC button pulsante_6x6.jpg to be pressed to continue the boot procedure.

The controller waits 5 seconds before continuing with the startup stage, without waiting for a button to be pressed.

When the situation does not allow to continue the startup stage (tipo B), the led led_lamp.jpgerr flashes continuously.

SYSTEM BOOTING

During the condition SELF-DIAGNOSTICS and SYSTEM BOOTING on the instrument with the display, you see some important information about the system as shown in the following picture:

:important:WARNING: The values shown in the diagram are examples and may change depending on the instrument in question.
List of informations
Nr.MessageDescription
1 Boot status: POWER-ONDisplays the boot status:
POWER-ON Sterting the instrument
INIT Initializing application downloads
RESTART Restart the instrument software
BACKUP Backup operation
RESTORE Restore operation
2 Firmware: 1K31F-30.5.6Displays the name, version, major release and minor release of the firmware. Example:
1K31F Firmware name
30 Version
5 Major release
6 Minor release (build)
3 S/N: 12345678Serial number of the instrument.
4 Date(DMY)/Time: 31/12/2010 - 12:34:56Clock and calendar:
GG/MM/YYYY - HH:MM:SS
5 Dip-Switch = 0x2EYou receive a “hexadecimal value representing the status of the switch SW1.
Is equivalent to the value of the system variable SYS002.
6 MMC: PRESENT 510/31250 KBIf you inserted the MMC/SD, at this stage appear the device data as used KB (510) and total KB (31250).
In case the device does not exist message appears: “not present !”
7 NAND: PRESENT 40510/63794 KBIt checks the internal device NAND and and then displays the used KB and the total KB.
In the event that the device is not found, an error is reported and appears “NAND: NOT PRESENT !”
8 Touch Screen: PRESENTIn the instruments with touch screen, it is detected and then checks the calibration data.
In the event that should still be performed calibration, you receive the message “CALIBRATION REQUIRED !”.
The touch calibration is possible with the system function “Touch Calibration”.
9 ETHERNET: IP = 192.168.0.253
NM = 255.255.255.0
GW = 0.0.0.0
FIXME Negli strumenti dotati di interfaccia ethernet, vengono visualizzati i parametri relativi all'indirizzo ip (IP), maschera di rete (NM) e gateway (GW).
La modifica di questi valori è possibile con la funzione di sistema “Set Ethernet communic. parameter”
10 BACKUP: VALID
QCL App: 25/04/2001 - 16:58:07 MATCH
QCL Dat: 25/04/2001 - 16:58:37 MATCH
QTP App: 25/04/2001 - 17:01:15 MATCH
Viene verificata la presenza in NAND di un backup valido e quindi vengono visualizzati i dati di data e ora di creazione dei files di backup relativi all'applicativo QCL (QCL App), ai dati dell'applicativo QCL (QCL Dat) e all'applicativo QTP (QTP App).
Se dopo la scritta “BACKUP” viene visualizzato “VALID” significa che il backup può essere correttamente ripristinato mediante funzione di sistema di “Restore from NAND”.
Se dopo la scritta “BACKUP” viene visualizzato “NOT PRESENT” significa che il backup non è presente.
Se dopo la scritta “BACKUP” viene visualizzato “NOT VALID” significa che il backup non può essere correttamente ripristinato in quanto i checksum dei tre files di cui è composto non sono tra di loro congruenti. Dopo ogni file (QCL App, QCL Dat e QTP App), oltre alle informazioni di data e ora di creazione, viene anche visualizzata un'ulteriore informazione:
“MATCH” indica che il file è coerente con quello dell'applicazione in RUN.
“NO MATCH” indica che il file non è coerente con quello dell'applicazione in RUN.
“SIZE ERROR” indica che la dimensione del file non è valida, forse perché la procedura di scrittura non si è conclusa correttamente.
“NOT PRESENT” indica che il file non è presente.
11 Press F1/FUNC for 2s to System FunctionsLa visualizzazione di questo messaggio indica che la pressione per almeno 2 secondi del tasto F1 o del pulsante FUNC permette di accedere alle funzioni di sistema come descritto nella Procedura. Il messaggio rimane visibile per 4 secondi.
12 !!! WARNING detected !!!
Press FUNC or F1 to continue
Se durante le precedenti fasi, vengono visualizzati dei messaggi di warning, che non pregiudicano il funzionamento del sistema, per permettere all'operatore di leggere con facilità lo schermo viene atteso un tempo di circa 20 secondi.
Per non attendere e proseguire prima, premere il tasto F1 o il pulsante FUNC.
13 !!! ERROR detected !!!
Press FUNC or F1 to continue
Messaggio visualizzato se nelle precedenti fasi, vengono visualizzati dei messaggi di errore.
Per proseguire viene richiesto di premere il tasto F1 o il pulsante FUNC.

:important:ATTENZIONE: I valori riportati in figura sono un esempio e possono cambiare a seconda dello strumento in questione.
Per gli strumenti senza display, durante questa fase non vengono riportate informazioni.